3-349-780-03
1/2.14
GMC-I Messtechnik GmbH
SC30, SC40-B/-C, SC50-E
Split-Core Current Transformers
SC50-ESC40
SC30
Application
Thanks to their compact design, the split-core current transform-
ers are especially suited for use in areas of restricted access and
confined space. The separable core makes it easier to install the
transformers on cables or rails. The split-core current transform-
ers are the right choice when an interruption of the electrical cir-
cuit is difficult or a measuring instrument has to be easily and
quickly refitted. The safe installation of the primary lead in the cur-
rent transformer is guaranteed by the mechanical design and is
confirmed by a distinctly audible click sound. Two UV proof cable
ties, which are part of the standard equipment, help to fix the
transformer additionally.
Technical Characteristics
Ambient Conditions
Deployment
indoor
Ambient temperature
–10 °C ... + 55 °C
Storage temperature
–20 °C ... + 70 °C
Relative humidity 5% ... 85%, no condensation allowed
Pollution degree 2
Protection class IP20
Only suited for insulated primary conductors
Conditions of Use
Standard IEC 61869-2
Rated short-term
thermal current (Ith) 60 x Ipr/1s
Rated continuous
thermal current (Icth) 100%
Rated insulation level 0.72/3/- kV
Rated frequency 50/60 Hz
Material (housing) PA 6.6, UL94:V2
Class of insulation E (120 °C)
Cable opening
SC30: for leads with a max. dia. of 18 mm
SC40-B: for leads with a max. dia. of 18 mm
SC40-C: for leads with a max. dia. of 28 mm
SC50-E: for leads with a max. dia. of 42 mm
Length and cross-section of secondary lead as a function of:
SC30: …/1A: L = 3 m 0.,5 mm²
SC40-B: …/1A: L = 3 m 0.5 mm²
…/5A: L = 0.5 m 1.5 mm²
SC40-C: …/1A: L = 3 m 0.5 mm²
…/5A: L = 0.5 m 1.5mm²
SC50-E …/1A: L = 5 m 0.5 mm²
…/5A: L = 3 m 1.5 mm²
Weight SC30: …/1A: 200 g
SC40-B: …/1A: 360 g
…/5A: 300 g
SC40-C: …/1A: 310 g
…/5A: 250 g
SC50-E …/1A: 525 g / 725 g
…/5A: 650 g / 850 g
Compact, split-core current transformers for primary nominal
current from 60 A … 1000 A and secondary nominal current
of 1 A or 5 A.
Very easy and time-saving installation thanks to split-core
design.
Particularly suited for retrofit purposes since the dismantling of
primary leads is not necessary
Allows for retrofitting without interrupting mains power supply
Compact design allows for use in areas with restricted access
and confined space
Clearly audible click sound confirms proper installation. Addi-
tional safety is provided by UV proof cable ties.
Accuracy class: 0.5, 1 or 3, depending on type

Vraag over de Gossen SC50-E?

Wanneer u een vraag heeft over de "Gossen SC50-E" kunt u die hier stellen. Zorg voor een duidelijke omschrijving van uw probleem zodat andere gebruikers en/of de redactie u van een passend antwoord kunnen voorzien.

Koop gerelateerde producten:

Product specificaties

Technische details
Kleur van het product Zwart
Certificering CE, RoHS
Diameter van de kabel 42 mm
Aantal posities 1
Werkingsklasse 1
Energie
Nominale input voltage 720 - 3000 V
Nominale stroom output 1 A
Gewicht en omvang
Breedte 66.2 mm
Diepte 66 mm
Hoogte   97 mm
Gewicht   725 g